70
Appendix A Technical Specifications
Accuracy, %
Parameter
Full scale
Rdg FS Conditions
Range
Display resolution (%Rdg)
@ range
2
Apparent energy
Under conditions of Class 0.5S
(IEC 687-1992-6)
1
0 to
999,999 MVAh
1 kVAh @ 1 to 999,999 kVAh
10 kVAh @ 1000 to 9,999.99 MVAh
100 kVAh @ 10,000 to 99,999.9 MVAh
1MVAh @ 100,000 to 999,999 MVAh
PT = external potential transformer ratio
CT, CT Primary Current = primary current rating of external current transformer
FSU = voltage full scale
FSI = current full scale
U1 = voltage fundamental
I1 = current fundamental
1
Voltage 70% to 120% FS and current 2% to 120% FS
2
Higher resolution is achievable via communications
3
Fundamental voltage 70% to 110% FS and fundamental current 10% to 100% FS, voltage THD
≥
5%, current THD
≥
10% up to
20
th
harmonic.
Additional Notes
1. Accuracy is expressed as
±
(percentage of r percentage of full scale)
±
1 digit. This does not include inaccuracies
introduced by the user's potential and current transformers.
2. Specifications assume: voltage and current waveforms with THD
≤
5% for kvar, kVA and PF; reference operating temperature:
20-26
°
C.
3. Ordinary measurement error is considerably less than the specified accuracy which indicates maximum error.
4. Harmonic real time values assume errors averaged over 10-20 readings.
Содержание PM172EH Series
Страница 1: ...Series PM172EH Powermeters Installation and Operation Manual BG0361 Rev A2 ...
Страница 90: ...84 Index NOTES ...