![Satec PM172EH Series Скачать руководство пользователя страница 32](http://html.mh-extra.com/html/satec/pm172eh-series/pm172eh-series_installation-and-operation-manual_1200381032.webp)
26
Chapter 4 Setup Menus
4.5 Analog Output Setup Menu
[This section is relevant to instruments ordered with this option]
Î
Î
Î
Î
This menu allows you to set up an output value and its zero and full
scales for either of the two internal analog output channels. Table 4-3
explains the analog output setup options, and Table 4-4 lists all
measurement parameters that can be directed to analog output.
Output parameter
Zero-scale output
Full-scale output
To select an analog channel:
9
Use the up/down arrow keys to select the desired analog output
channel.
To view the setup options for the selected channel:
9
Press to activate the middle window.
9
Use the up/down arrow keys to scroll to the desired option. The
value associated with this option is displayed in the lower window.
To change the setup options for the selected channel:
9
Press to activate the lower window.
9
Use the up/down arrow keys to scroll to the desired value.
9
Press to store the selected value, or press to
leave the value unchanged.
9
Press again to store the setup for the channel.
To quit the setup without changes:
9
From the middle or lower window, press .
To quit the menu:
9
From the upper window, press or .
NOTES
1. Except for the signed power factor, the output scale is linear within the value
range. The scale range will be inverted if the full scale specified is less than the
zero scale.
2. The output scale for the signed power factor is symmetrical with regard to
±
1.000 and is linear from -0 to -1.000, and from 1.000 to +0 (note that -1.000
≡
+1.000). Negative power factor is output as [-1.000 minus measured value], and
non-negative power factor is output as [+1.000 minus measured value]. To define
An. 1
828
Hi
An. 1
rt U1
Outp
An. 1
0
Lo
SELECT
SELECT
ENTER
ESC
ENTER
ESC
ESC
ENTER
SELECT
CHG
Aout
Ï
Ð
ENTER
ENTER
Содержание PM172EH Series
Страница 1: ...Series PM172EH Powermeters Installation and Operation Manual BG0361 Rev A2 ...
Страница 90: ...84 Index NOTES ...