Chapter 4 Setup Menus
33
Table 4-6 Setpoint Setup Options (middle window)
Code Option
Description
LGC.1 - LGC.4 Logical operator
(OR/AND) for the
trigger
Connects the trigger condition to previous
setpoint conditions using specified logical
operator
trG.1 - trG.4
Trigger parameter
The measurement parameter or signal to be
monitored by the setpoint.
On.1 - On.4
Operate limit for the
trigger
The threshold at which the setpoint
becomes operative.
OFF.1 - OFF.4 Release limit for the
trigger
The threshold at which the setpoint is
released (becomes inoperative).
Act.1 - Act.4
Setpoint action
The action performed when the setpoint is
operative.
On d
Operate delay
The time delay (seconds) before operation
when the operate condition is fulfilled.
OFF d
Release delay
The time delay (seconds) before release
when the release condition is fulfilled.
Table 4-7 Setpoint Triggers (lower window, when middle window is
trG)
Code Parameter Unit
Range
1
nonE Setpoint
disabled
2
Status Inputs
4
St1.On
Status input #1 ON
St2.On
Status input #2 ON
St1.OFF
Status input #1 OFF
St2.OFF
Status input #2 OFF
Pulse Inputs
4
PlS.In.1
Pulse input #1
PlS.In.2
Pulse input #2
Counters
4
Cnt.1
High counter #1
0 to 999999
Cnt.2
High counter #2
0 to 999999
Cnt.3
High counter #3
0 to 999999
Cnt.4
High counter #4
0 to 999999
Relay Status
4
rL1.On
Relay #1 ON
rL2.On
Relay #2 ON
rL1.OFF Relay #1 OFF
rL2.OFF Relay #2 OFF
Voltage disturbance
4
U.diSt Voltage
disturbance
5
%
1 to 100
Phase Reversal
4
POS.Ph.r
Positive phase rotation reversal
c
NEG.Ph.r Negative phase rotation reversal
c
Содержание PM172EH Series
Страница 1: ...Series PM172EH Powermeters Installation and Operation Manual BG0361 Rev A2 ...