Table 5-48 Event Log Window Registers
Parameter
Offset
Size,
byte
Direction
Range
0
2
R
0-59,
97 = record corrupted
98 = no more events
99 = no events logged
Minute
+1
2
R
0-59
Hour
+2
2
R
0-23
Day
+3
2
R
1-31
Month
+4
2
R
1-12
Year +5
2
R
0-99
Event cause
+6
2
R
see Table 5-46
Event origin
+7
2
R
see Table 5-46
Log value (16-bit
register/32-bit counter)
+8
+9
4
R
see Table 5-46
Event effect
+10
2
R
see Table 5-46
Event target
+11
2
R
see Table 5-46
The log value can be read in one or two registers depending on the value type. For the value length and
conversion scales, refer to Table 5-26.
Table 5-46 Event Log Parameters
Event
cause
Event cause code
Event origin
(location)
Log value
Event effect
Event target
Setpoint
event
Trigger parameter
ID high byte (see
Table 5-29)
Trigger parameter ID
low byte (see Table
5-29)
Trigger
parameter
value (see
Table 5-29)
225 = setpoint
operated
226 = setpoint
released
Setpoint
number = 0-15
Comm.
activity
91 Data
location
code
(see Table 5-47)
N/A
See Table 5-48
See Table 5-48
Front panel
activity
92 Data
location
code
(see Table 5-47)
N/A
See Table 5-48
See Table 5-48
Self-check 93
Data
location
code
(see Table 5-47)
N/A
See Table 5-48
See Table 5-48
External
event
99
0 = power down
8 = power up
N/A N/A
N/A
Table 5-47 Data Location Codes
Location code
Description
3
Data keeping memory
8 Real-time
clock
16 Event/alarm
setpoint
Table 5-48 Event Effect Codes
Effect code
Description
Target
96
Clear energy registers
N/A
97 Clear
maximum
demand
registers
0 = all demands
1 = power demands
2 = volt/ampere demands
98
Clear TOU energy registers
N/A
99
Clear TOU maximum demand
registers
N/A
100
Clear counters
0 = all counters
1-4 = counter #1-#4
101
Clear Min/Max log registers
N/A
102 Clear
event
log
N/A
103
Clear data log
0-7 = log #1-#8
16 = all data logs
225
Setpoint operated
0-15 = setpoint #1-#16
226
Setpoint released
0-15 = setpoint #1-#16
241
Setpoint disabled
0-15 = setpoint #1-#16
245 RTC
set
N/A