32
Trigger parameter
Trigger Size,
Unit
Limit/scale
Con-
ID
byte
Low
High
version
High sliding window kVA demand (E)
5643
2
1kVA
0
Pmax
LIN3
High accumulated kW import demand (E)
5647
2
1kW
0
Pmax
LIN3
High accumulated kVA demand (E)
5649
2
1kVA
0
Pmax
LIN3
High predicted kW import demand (E)
5650
2
1kW
0
Pmax
LIN3
High predicted kVA demand (E)
5652
2
1kVA
0
Pmax
LIN3
For parameter limits, see note
to Table 5-1
Voltages are transmitted in 1V units, currents in 1 A units, and powers in 1 kW/kvar/kVA units.
The setpoint is operated when the actual phase sequence does not match the indicated phase rotation.
The actual frequency range is 45.00 - 65.00 Hz (20.00 - 65.00 Hz - special order).
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring
mode, they will be line-to-line voltages.
(E) available in the PM171E
Table 5-30 Setpoint Actions
Action
Action ID
No action
0
Operate relay #1
12288
Operate relay #2
12289
Increment counter #1 (E)
16384
Increment counter #2 (E)
16385
Increment counter #3 (E)
16386
Increment counter #4 (E)
16387
Clear counter #1 (E)
16896
Clear counter #2 (E)
16897
Clear counter #3 (E)
16898
Clear counter #4 (E)
16899
Clear all counters (E)
25600
Reset total energy (E)
24576
Reset all total maximum demands (E)
24832
Reset power maximum demands (E)
24833
Reset volt/ampere maximum demands (E)
24834
Reset TOU energy (E)
25088
Reset TOU maximum demands (E)
25344
Clear Min/Max registers (E)
25856
Event log (E)
28674
Data log #1 (E)
28928
Data log #2 (E)
28929
Data log #3 (E)
28930
Data log #4 (E)
28931
Data log #5 (E)
28932
Data log #6 (E)
28933
Data log #7 (E)
28934
Data log #8 (E)
28935
(E) available in the PM171E
In the PM171E, operate/release actions via relays are automatically recorded to the event log whenever an
electrical quantity, status input, or phase reversal trigger is used.
Either setpoint transition (both operate and release) is recorded to the event log.
5.15 Pulsing Setpoints Registers
Table 5-31 Pulsing Registers
Relay
Setup registers (see Table 5-32)
Relay #1
2892-2893
Relay #2
2894-2895