34
Table 5-38 Digital Inputs Identifiers
Discrete input
ID
Not allocated
0
Digital input # 1
1
Digital input # 2
2
5.18 Log Memory Partitions Setup Registers
Table 5-39 Memory Partitions Setup Registers
Partition
Number
Memory partition
Setup registers
(see Table 5-40)
0 Event
log 3660-3665
1
Data log #1
3668-3673
2
Data log #2
3676-3681
3
Data log #3
3684-3689
4
Data log #4
3692-3697
5
Data log #5
3700-3705
6
Data log #6
3708-3713
7
Data log #7
3716-3721
8
Data log #8
3724-3729
Table 5-40 Partition Setup Registers
Parameter
Offset
Size,
byte
Direction
Range
The number of records in the
partition
+0 2 R/W
0-65535,
0 = delete partition
The number of log parameters in the
record for a data log partition (for an
event log partition, write 0)
+1 2 R/W
0-16
Partition type
+2
2
R/W
0 = non-wrap
1 = wrap around
Record size, byte
+3
2
R
Partition size, byte
+4
+5
4 R
0-524288
These registers allow you to allocate a memory partition for logging and to specify the partition size and type.
Before allocating a partition, it is recommended to check the available memory by reading the extended memory
status registers. To help you in planning memory, Table 5-41 shows the record size for each partition.
Note that the existing partition may not be resized. To change the partition properties, you should first delete a
partition and then reallocate it with the desirable properties. To delete a partition, write zero into the first
partition's register.
When allocating a memory partition, all partition registers must be written at once using a single request. After
reallocation of memory, the instrument performs the memory optimization and will not respond to the host
requests for approximately 1 second per 128 Kbyte of memory.
Writing into registers at o3, +4 and +5 does not affect the register contents. No error will occur.
Table 5-41 Partitions' Record Size
Partition
Record size, byte
Event log
14
Data log
8 + 4
∗
(NUMBER OF PARAMETERS)