5.3 User Selectable Options Setup Registers
Table 5-3 User Selectable Options Registers
Parameter
Register Size,
byte
Direc-
tion
Range
Power calculation mode
2376
2
R/W
0 = using reactive power,
1 = using non-active power
Energy roll value (E)
2377
2
R/W
0 = 1
×
104
1 = 1
×
105
2 = 1
×
106
3 = 1
×
107
4 = 1
×
108
5 = 1
×
109
Phase energy calculation mode (E)
2378
2
R/W
0 = disable, 1 = enable
Analog output option
2379
2
R/W
0 = none
1 = 0-20 mA
2 = 4-20 mA
3 = 0-1 mA
4 =
±
1 mA
Analog expander output
2380
2
R/W
0 = none
1 = 0-20 mA
2 = 4-20 mA
3 = 0-1 mA
4 =
±
1 mA
(E) available in the PM171E (read as 65535 in the PM171P)
For short energy registers (see Table 5-1), the maximum roll value will be 1
×
10
8
for positive readings and
1
×
10
7
for negative readings.
Do not enable the analog expander output if the analog expander is not connected to the instrument,
otherwise the computer communications will become garbled.