28
Table 5-23 Analog Output Parameters
Output parameter
Data
Size,
Unit
Scale
Con-
ID
byte
Low
High
version
None
None
0 2
N/A N/A
NONE
Real-time values per phase
Voltage L1/L12
3072
2
1V 0
Vmax
LIN3
Voltage L2/L23
3073
2
1V 0
Vmax
LIN3
Voltage L3/L31
3074
2
1V 0
Vmax
LIN3
Current L1
3075
2
1A
0
Imax
LIN3
Current L2
3076
2
1A
0
Imax
LIN3
Current L3
3077
2
1A
0
Imax
LIN3
Real-time total values
Total kW
3840
2
1kW
-Pmax
Pmax
LIN3
Total kvar
3841
2
1kvar
-Pmax
Pmax
LIN3
Total kVA
3842
2
1kVA
0
Pmax
LIN3
Total PF
3843
2
0.001
-1.000
1.000
LIN3
Total PF Lag
3844
2
0.001
0
1.000
LIN3
Total PF Lead
3845
2
0.001
0
1.000
LIN3
Real-time auxiliary values
Frequency
4098
2
0.01Hz
0
100.00
LIN3
Average values per phase
Voltage L1/L12
4352
2
1V 0
Vmax
LIN3
Voltage L2/L23
4353
2
1V 0
Vmax
LIN3
Voltage L3/L31
4354
2
1V 0
Vmax
LIN3
Current L1
4355
2
1A
0
Imax
LIN3
Current L2
4356
2
1A
0
Imax
LIN3
Current L3
4357
2
1A
0
Imax
LIN3
Average total values
Total kW
5120
2
1kW
-Pmax
Pmax
LIN3
Total kvar
5121
2
1kvar
-Pmax
Pmax
LIN3
Total kVA
5122
2
1kVA
0
Pmax
LIN3
Total PF
5123
2
0.001
-1.000
1.000
LIN3
Total PF Lag
5124
2
0.001
0
1.000
LIN3
Total PF Lead
5125
2
0.001
0
1.000
LIN3
Average auxiliary values
Neutral current
5377
2
1A
0
Imax
LIN3
Frequency
5378
2
0.01Hz
0
100.00
LIN3
Present demands
Accumulated kW import
demand (E)
5647 2 1kW
0
Pmax LIN3
Accumulated kVA demand (E)
5649
2
1kVA
0
Pmax
LIN3
For parameter limits, see note
to Table 5-1.
Voltages are transmitted in 1V units, currents in 1A units, and powers in 1 kW/kvar/kVA units.
The actual frequency range is 45.00 to 65.00 Hz (20.00 - 65.00 Hz - special order).
The output scale for signed (bi-directional) power factor is symmetrical with regard to
±
1.000 and is linear
from -0 to -1.000, and from 1.000 to +0 (note that -1.000
≡
+1.000). Negative power factor is output as [-1.000
minus measured value], and non-negative power factor is output as [+1.000 minus measured value]. To
define the entire range for power factor from -0 to +0, the scales would be specified as -0/0. Because of the
fact that negative zero may not be transmitted, the value of -0.001 is used to specify the scale of -0, and both
+0.001 and 0.000 are used to specify the scale of +0. To define the range of -0 to 0, you must send
-0.001/0.001 or -0.001/0.
When the 4LN3 or 3LN3 wiring mode is selected, the voltages will be line-to-neutral; for any other wiring
mode, they will be line-to-line voltages.
(E) available in the PM171E