30
Table 5-31 Setpoint Setup Registers
Parameter
Offset
Size, byte
Range
Trigger ID
+0
2
see Table 5-29
1
2
see
Table
5-30
Operate delay
+2
2
0-9999 (x 0.1 sec)
Release delay
+3
2
0-9999 (x 0.1 sec)
Operate limit
+4
+5
4 see
Table
5-29
Release limit
+6
+7
4 see
Table
5-29
1. The setpoint is disabled when the first trigger ID is set to NONE. To disable the setpoint, write zero into
this register.
2. When writing the setpoint registers (except the event when the setpoint is to be disabled), it is
recommended to write all the setpoint registers using a single request, or disable the setpoint before
writing into separate registers. Each value being written is checked for compatibility with the other
setpoint parameters; if the new value does not conform to these, the request will be rejected.
3. Operate and release limits for the trigger parameters and their conversion scales are indicated in Table
5-29. Each limit value occupies two contiguous registers, the first of which (low word) contains the limit
value, and the second (high word) is reserved for long parameters. This register is always read as zero.
When written, its value is ignored.
4. Limits indicated in Table 5-29 by a N/A mark are read as zeros. When writing, they can be omitted or
should be written as zeros.
5. When a setpoint action is directed to a relay allocated to output energy pulses, an attempt to re-allocate
it for a setpoint will result in a negative response.
Table 5-29 Setpoint Trigger Parameters
Trigger parameter
Trigger Size,
Unit
Limit/scale
Con-
ID
byte
Low
High
version
None
None
0 2
N/A
N/A
NONE
Internal events (E)
kWh import pulse
1024 2
N/A N/A NONE
kWh export pulse
1025 2
N/A N/A NONE
kvarh import pulse
1027 2
N/A N/A NONE
kvarh export pulse
1028 2
N/A N/A NONE
kvarh total pulse
1029 2
N/A N/A NONE
kVAh total pulse
1030 2
N/A N/A NONE
Start new demand interval
1031 2
N/A N/A NONE
Start new tariff interval
1032 2
N/A N/A NONE
Start new volt/ampere demand interval
1033 2
N/A N/A NONE
Start new sliding window demand interval
1034 2
N/A N/A NONE
Timers (E)
Timer #1
1280
2
N/A
N/A
NONE
Timer #2
1281
2
N/A
N/A
NONE
Status inputs
Status input #1 ON
1536
2
N/A
N/A
NONE
Status input #2 ON
1537
2
N/A
N/A
NONE
Status input #1 OFF
34304 2
N/A
N/A
NONE
Status input #2 OFF
34305 2
N/A
N/A
NONE
Pulse inputs (E)
Pulse input #1
1792
2
N/A
N/A
NONE
Pulse input #2
1793
2
N/A
N/A
NONE
Phase reversal
Positive phase rotation reversal
35073 2
N/A
N/A
NONE
Negative phase rotation reversal
35074 2
N/A
N/A
NONE
Pulse counters
High pulse counter #1
2560
2
0
10
6
-1 NONE
High pulse counter #2
2561
2
0
10
6
-1 NONE
High pulse counter #3
2562
2
0
10
6
-1 NONE