9
3.6 Exception Responses
The instrument sends an exception response when errors are detected in the received message. To
indicate that the response is notification of an error, the high order bit of the function code is set to 1.
Exception Response
Instrument
Address
Function (high
order bit is set to 1)
Exception
Code
Error Check
1 byte
1 byte
1 byte
2 byte
Exception response codes:
01
- Illegal
function
02
- Illegal
data
address
03
- Illegal
data
value
06
-
Busy, rejected message. The message was received without error, but the instrument is being
programmed from the keypad (only for requests accessing setup registers).
NOTE
When the character framing, parity, or redundancy check detects a communication error, processing of
the master's request stops. The instrument will not act on or respond to the message.