20
Sealed Control Points
Some Control Points are sealed. These are settings that, once programmed, seldom or never require a change. To
make it less likely that a sealed setting be changed by accident, you must hold the A button for 5 seconds before it
is possible to make an adjustment.
CONTROL POINTS
Control Value
Factory
Point Description
Range
Setting
Comments
Number
00
Back check
3 – 60
35
The angle at which the opening door slows from
angle
units
opening speed to back check speed. Each unit in
the value range approximately 2 degrees
01
Fully open position
3 – 60
42
The angle of the door when it is fully open.
units
• Must be greater than the back check angle
• Maximum door opening angle: 100 degrees
• Each unit in the value range =
approximately 2 degrees per unit
02
Latching speed
15 – 60
15
The angle at which the closing door slows from
starting point angle
units
closing speed to latching speed.
Recommendation: 10 degrees
• Each unit in the value range =
approximately 2 degrees
• See Control Points Affecting Speed and Closure.
03
Operator force
1 – 10
4
The amount of force the Operator applies to
Sealed Control Point
relative
the door to open or close it.
1 = minimum force
10 = maximum force
• The lighter the door, the less Operator force
is required.
• Operator force affects obstruction sensitivity;
see Control Points 12 and 19.
• See Control Points Affecting Speed and Closure.
WARNING:
CLOSING FORCE MUST NOT EXCEED
15 LB FOR A LOW-ENERGY APPLICATION.
04
Delay time
0 –15
1.2
When the Operator receives an “open” delayed
sec
impulse, the latching device is released immediately;
however the opening of the door is delayed to give
the latch time to retract.
0 = no delay
15 = about 15 sec delay
SEALED CONTROL POINTS