3
WARNING
The SARGENT 2600 Series Low-Energy Door Operator is intended to be used in low-energy handicap
applications. Guidelines for low-energy can be found in ANSI Standard A156.19, American National Standard for
Power Assist and Low-Energy Power Operated Doors.
Generally speaking, low-energy doors move slowly, and therefore generate minimal levels of kinetic energy.
SARGENT recommends that the hold-open time for a low-energy door be not less than 10 seconds. Also, local fire
codes requirements for hold-open time should be taken into consideration.
Minimum opening and closing times for doors of various widths and weights are summarized in the table below.
Minimum Opening Time to Back Check or 80 deg or
Minimum Closing Time from 90 deg to Latch Check or 10 deg
Doors of other weights and widths can be calculated using the formula:
T= D W Where:
T = Time in sec
133 lb-ft
D = Door width in inches
W = Door weight in lb
CLOSING FORCE MUST NOT EXCEED 15 LB FOR A LOW-ENERGY APPLICATION. IF CLOSING FORCE
EXCEEDS 15 LB, THE DOOR WILL NOT MEET THE REQUIREMENTS OF ANSI STANDARD A156.19, AMERICAN
NATIONAL STANDARD FOR POWER ASSIST AND LOW ENERGY POWER OPERATED DOORS.
LATCHING SPEED MUST BE SUCH THAT THE DOOR TAKES AT LEAST 1.5 SEC TO MOVE FROM LATCHING
SPEED STARTING POINT TO FULLY CLOSED.
WHEN INSTALLATION IS COMPLETE, SET CONTROL POINT 15 TO 1, FIRE DOOR MODE. WHEN A FIRE ALARM
IS ACTIVATED, THE DOOR IS OPENED MANUALLY AND CLOSED UNDER POWER. IF THIS SETTING IS NOT 1,
THE DOOR WILL NOT ACHIEVE UL COMPLIANCE.
WARNINGS AND GUIDELINES
“D” Door
Width in
“W” Door Weight in Pounds
Inches
100
125
150
175
200
30
3.0 sec
3.0 sec
3.0 sec
3.0 sec
3.5 sec
36
3.0 sec
3.5 sec
3.5 sec
4.0 sec
4.0 sec
42
3.5 sec
4.0 sec
4.0 sec
4.5 sec
4.5 sec
48
4.0 sec
4.5 sec
4.5 sec
5.0 sec
5.5 sec