Fire Alarm Detection Jumper
JUMPER POSITION
FUNCTION / OPERATION
"ON"
Normally Open Fire Alarm contact
required
"OFF"
Normally Closed Fire Alarm contact
required
13
SET ALARM JUMPERS
BATTERY ALARM AND FIRE ADAPTER
1
2
3
4
5
6
7
8
9
POWER ALARM TERMINATIONS
BATTERY ALARM TERMINATIONS
REMOTE FIRE
ALARM N.C. CONTACT
INTERNAL CONNECTIONS
WARNING:
Fire Alarm jumpers MUST
be properly set with connectors from an
approved fire system. Check your local
code requirements.
Power Alarm - Terminations 1 & 2 on the
Fire Adapter Board
Normally Open Contacts close when the
main 115 VAC power is disrupted. This
action is unaffected by the jumper
positions or loss of battery power.
Battery Alarm Jumper
JUMPER POSITION
FUNCTION / OPERATION
"ON"
Maintained Low Battery Alarm:
Normally Open contacts 3 & 4 close,
initiating alarm. Must be Reset by
push button.
"OFF"
Momentary Low Battery Alarm: Low
or disconnected battery condition
close contacts 3 & 4 momentarily.