8-4-6. Diagnosis of overload and discharge malfunction
< Main Detection Points >
•
Is electric expansion valve well connected ? Is it damaged ?
•
Is refrigerant leaked ?
•
Is overload wire connection normal ?
< Malfunction Diagnosis Process >
Finish
Replace electric
expansion valve.
20 min after
de-energization of
complete unit.
Yes
Yes
Yes
Yes
No
No
Is electric
expansion valve well
connected ?
Refrigerant leakage,
recharge the refrigerant.
Remove malfunction ?
Replace parts of outdoor
electric box.
Remove malfunction ?
No
Is overload
wire reliably
connected ?
Adjust connecting wire.
No