<Outline>
During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation
and then prevent freezing of the indoor heat exchanger. (The signal from the indoor unit must be divided into
the zones as the followings).
<Detail>
•
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 seconds from operation start.
7-2-6. Freeze-up Protection Control
<Outline>
During heating operation, the signals being sent from the indoor unit allow the operating frequency limitation
and prevent abnormal high pressure. (The signal from the indoor unit must be divided as follows).
<Detail>
•
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 seconds from operation start
•
Control in Each Zone
The heat exchanger intermediate temperature of indoor unit controls the following.
•
Limitation of current drooping and stop value according to the outdoor air temperature
7-2-7. Heating Peak-Cut Control
(1) In case the operation mode is cooling
•
The current droops when outdoor air temperature becomes higher than a certain level (model by model).
(2) In case the operation mode is heating
•
The current droops when outdoor air temperature becomes higher than a certain level (model by model).
A
B
C
D
E
Return/Reset zone
Up zone
Keep zone
Drooping zone
Stop zone
Heat exchanger
thermistor temperature
Reset zone
Up zone
Keep zone
Drooping zone
Stop zone
Heat exchanger
thermistor temperature
31
Содержание SAP-CRV12AEH
Страница 13: ...3 DIMENSIONAL DATA Indoor Unit SAP KRV9AEH SAP KRV12AEH 770 201 283 548 5 258 5 126 5 770 283 13 ...
Страница 14: ...Outdoor Unit SAP CRV9AEH SAP CRV12AEH 708 658 275 550 317 470 299 14 ...
Страница 67: ...INSTRUCTION MANUAL SAP KRV9AEH SAP CRV9AEH SAP KRV12AEH SAP CRV12AEH OI 852 6 4181 180 00 1 APPENDIX A A 1 ...
Страница 107: ......
Страница 108: ...SANYO Electric Co Ltd Osaka Japan June 2010 Printed in Japan B ...