(1) Indoor Temperature Sensor
Detect malfunctions of temperature sensor any time.
(2) Indoor Pipe Temperature Sensor
In defrosting period, the temperature sensor malfunction will not be detected.
5 minutes after finishing defrosting, the system begins to detect the temperature sensor malfunction.
In other times, the temperature sensor malfunction will be detected.
(3)
Protection of Temperature Sensor
(3-1) When short-circuit occurs to the temperature sensor for 30 seconds
The temperature sensor overheats. In this case, the complete unit will stop for protection.
At the same time, the temperature protection and temperature sensor malfunction will be shown.
(3-2) When break-circuit occurs to the temperature sensor for 30 seconds
The unit will stop and the temperature sensor malfunction will be displayed.
7-2-10. Temperature Sensor Malfunction Detection