W-2WAY ECO-i SYSTEM
Remote Controller Functions
4
- 4
2. Detailed Settings Function
4
This allows the system address, indoor unit
address, and other settings to be made for the
individual or group-control indoor unit to which
the remote controller used for detailed settings is
connected.
When detailed settings mode is engaged,
operation stops at the individual or group-control
indoor unit where the remote controller used for
detailed settings is connected. Simple settings
items can also be set at this time.
<Procedure>
➀
Press and hold the
,
and
buttons
simultaneously for 4 seconds or longer.
➁
“
,” unit No. “
” (or “
” in the case
of group control), item code “
,” and settings
data “
” are displayed blinking on the
remote controller LCD display (Fig. 2).
At this time, the indoor unit fan (or all indoor unit
fans in the case of group control) begins operating.
➂
If group control is in effect, press the
button and select the address (unit No.) of the
indoor unit to set. At this time, the fan at the indoor
unit begins operating.
➃
Press the temperature setting
/
buttons to select the item code to change.
➄
Press the timer time
/
buttons to select the
desired setting data.
*
For item codes and setting data, refer to the
following page.
➅
Press the
button. (The display stops blinking
and remains lit, and setting is completed.)
➆
Press the
button to return to normal remote
controller display.
•
Fig. 2
RCS-TM80BG
2
1
6
5
1
7
3
4
W-2WAY ECO-i SYSTEM̲Eng.indb 4
W-2WAY ECO-i SYSTEM̲Eng.indb 4
2008/09/01 18:22:54