W-2WAY ECO-i SYSTEM
Remote Controller Functions
4
- 15
2. Detailed Settings Function
4
■
DC Fan Tap Change Procedure
<Procedure>
Be sure to turn the main power OFF before performing the steps below.
(1) Check the optional product that will be used from the table below.
Setting No.
Optional part name
Optional part No.
[1]
Super long-life fi lter
AFT-LS140A
Oil guard panel
PNR-S140AAG
Ammonia deodorizing fi lter
AFT-DS140AG-AM
Optical regeneration deodorizing fi lter
AFT-DS140AG-PC
[3]
High-performance fi lter, colorimetric 65% type
AFT-MS140A
High-performance fi lter, colorimetric 90% type
AFT-HS140A
Air cleaning unit
AFT-ES140A
Deodorant fi lter
AFT-DS140AG
Air-blocking material (for 3-direction discharge)
INS-DS140A
Air-blocking material (when a discharge duct is connected)
INS-DS140A
[6]
Air-blocking material (for 2-direction discharge)
INS-DS140A
Setting No. [1] : Go to (2).
Setting No. [3] : Go to (3).
Setting No. [6] : Go to (4).
(2) Setting No. [1]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP1 (2P, RED) on the indoor unit control PCB.
(3) Setting No. [3]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP3 (2P, YEL) on the indoor unit control PCB.
(4) Setting No. [6]
Open the cover of the electrical component box, and connect the supplied short circuit connector (2P, YEL) to short-circuit
pin TP6 (2P, WHT) on the indoor unit control PCB.
TP6
White Yellow Red
TP3 TP1
Indoor unit control PCB
Short-circuit pins (2P)
Also make the appropriate EEPROM settings.