2
2
- 8
W-2WAY ECO-i SYSTEM
Outdoor Unit Repair Procedures
4. Backup Operation
4-2-2. Backup operation by setting the failed compressor not to operate
Backup operation settings for each compressor
INV compressor
AC1 compressor
AC2 compressor
Setting for backup operation
OK
OK
Failed
DIP switch S010:
Turn BACK UP and AC2 ON.
OK
Failed
OK
DIP switch S010:
Turn BACK UP and AC1 ON.
OK
Failed
Failed
DIP switch S010:
Turn BACK UP, AC1, and AC2 ON.
Failed
OK
OK
DIP switch S010:
Turn BACK UP and INV ON.
Failed
OK
Failed
DIP switch S010:
Turn BACK UP, INV, and AC2 ON.
Failed
Failed
OK
DIP switch S010:
Turn BACK UP, INV, and AC1 ON.
sec2-document.qxd:sec2-document.qxd 08.8.22 1:39 PM Page 8