W-2WAY ECO-i SYSTEM
Control Functions
3-1. Compressors Mounted in the Outdoor Units
[SPW-C0705DXHN8, C0905DXHN8, C1155DXHN8, C1305DXHN8, C1405DXHN8]
INV
INV
Types 1305, 1405
Types 905, 1155
Compressor 2
Compressor 2
Compressor 1
Compressor 1
Compressor 3
Constant
speed
Constant
speed
Constant
speed
INV
Type 705
Compressor 1
Compressor 1
Compressor 2
Compressor 3
5 hp
6 hp
5 hp
5 hp
6 hp
6 hp
–––
–––
–––
–––
Scroll
Scroll
705*
905
1155
1305
1405
DC Inverter
DC Inverter
DC Inverter
DC Inverter
DC Inverter
Installed
compressor
Capacity
Rotary
hp = horsepower
* For both 50 Hz and 60 Hz.
3-2. Compressor Selection Rules
In cooling mode, all inverter compressors in the outdoor units are designed to operate simultaneously. All the
inverter compressors will stop at a time when the outdoor is stopped accordingly. Constant-speed compressors
run in order of the shortest amount of operating time. In heating mode, the inverter compressor with the shortest
amount of operating time runs at first followed by the compressors in order of the shortest amount of operating
time including inverter units.
* Immediately after installation, all compressors have an operating time of zero. In this case, the compressors
start in the following sequence: Inverter compressor > Constant-speed compressor 1 > Constant-speed com-
pressor 2.
Examples of accumulated operating time: ODU=Outdoor Unit
Suppose the following tentative system.
Compressor Selection Sequence in Cooling Mode:
All the inverter compressors are firstly selected simultaneously .
3. Compressor Control
ODU 1
ODU 2
OUD 3
Comp 1
Comp 2
Comp 3
100 hrs.
150 hrs.
110 hrs.
70 hrs.
160 hrs.
80 hrs.
140 hrs.
40 hrs.
90 hrs.
ODU 1
ODU 2
OUD 3
Comp 1
Comp 2
Comp 3
1st
6th
5th
1st
7th
3rd
1st
2nd
4th