W-2WAY ECO-i SYSTEM
Trouble Diagnosis
4. W-2WAY ECO-i Alarm Codes
With types 705, 905 and 1155, the INV compressor is compressor 1, and the constant-speed
compressor is compressor 2.
With types 1305 and 1405, the INV compressor is compressor 1, and the constant-speed
compressors (AC1, AC2) are compressors 2 and 3.
Alarm code
Alarm meaning
Page
E06
Outdoor unit failed to receive serial communication signals from indoor unit.
5
-9
E12
Automatic address setting start is prohibited.
5
-9
E15
Automatic address setting alarm (too few units)
5
-9
E16
Automatic address setting alarm (too many units)
5
-10
E20
No indoor units at automatic address setting.
5
-10
E24
Outdoor unit (INV) failed to receive communications from another outdoor
unit (constant-speed).
5
-10
E25
Outdoor unit address setting failure (duplication)
5
-11
E26
Mismatch in outdoor unit quantity
5
-11
E29
Outdoor unit failed to receive communication from outdoor unit (main)
5
-11
F04
Compressor 1 discharge temperature sensor trouble
5
-12
F05
Compressor 2 discharge temperature sensor trouble
5
-12
F22
Compressor 3 discharge temperature sensor trouble
5
-12
F06
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)
5
-13
F07
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)
5
-13
F08
Outdoor air temperature sensor trouble
5
-14
F12
Compressor intake temperature sensor trouble
5
-14
F16
High-pressure sensor trouble
5
-15
F17
Low-pressure sensor trouble
5
-16
F23
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)
5
-13
F24
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)
5
-13
F25
Gas temperature sensor trouble at outdoor heat exchanger 3
5
-13
F26
Liquid temperature sensor trouble at outdoor heat exchanger 3
5
-13
F31
Outdoor unit non-volatile memory (EEPROM) trouble
5
-16
H11
Constant speed compressor 2 overcurrent alarm
5
-17
H12
Constant speed compressor 2 lock current alarm
5
-17
H03
Compressor 1 CT sensor disconnected or short-circuit
5
-18
H06
Low-pressure switch activated
5
-19
H07
No-oil alarm
5
-20
H08
Compressor 1 oil detection sensor (connection) trouble
5
-20
H13
Compressor 2 CT sensor disconnected or short-circuit
5
-18
H15
Compressor 2 discharge temperature sensor disconnected
5
-18
H21
Compressor 3 overcurrent alarm
5
-17
H22
Compressor 3 lock current alarm
5
-17
H23
Compressor 3 CT sensor disconnected or short-circuit
5
-18
H25
Compressor 3 discharge temperature sensor disconnected
5
-18
H27
Compressor 2 oil detection sensor (connection) trouble
5
-20
H28
Compressor 3 oil detection sensor (connection) trouble
5
-20
H31
HIC trouble alarm
5
-21
L04
Outdoor system address duplication
5
-21
L10
Outdoor unit capacity not set
5
-22
L17
Outdoor unit model mismatch
5
-22
L18
4-way valve operation failure
5
-22