16. Backup Operation
[2] Disabling operation of 1 compressor
At the S010 switch on the PCB of the failed outdoor unit, turn ON the switch for the compressor to disable, and
turn ON the “backup” switch.
<S010 switch>
• In order to perform simultaneous backup operation for 2 or more compressors, use a combination of the switch
settings shown above.
W-2WAY ECO-i SYSTEM
Control Functions
1
1
- 29
INV
AC1
AC2
Backup
ON
OFF
(A) Compressor 2 backup
(B) Compressor 3 backup
ON
OFF
ON
OFF
(C) Close all service valves at the failed outdoor units.
(D) Reset the power at outdoor unit No.1.
* When the PCB of the main unit is normal, by implementing the above settings while leaving the communica-
tion lines between indoor and outdoor units as they are, backup operation of units are possible. In this case,
the outdoor unit that backed up all compressors is not identified as an outdoor unit, however, it can work as
the command controller.
INV+BU
INV+AC1+BU
INV+AC1+BU
INV+AC1+AC2+BU
INV+AC1+AC2+BU
8 hp
Switches to turn ON
Outdoor unit hp
10 hp
12 hp
14 hp
16 hp