Product Specifications
2-20
Samsung Electronics
Indoor Unit(cont.)
Q
Wall Mounted type(Neo Forte with EEV)
Model
AM022FNQDEH/TK
AM028FNQDEH/TK
AM036FNQDEH/TK
Power Supply
ø/V/Hz
1/220~240/50
1/220~240/50
1/220~240/50
Mode*
1)
HP
HP
HP
Performance
Capacity
Cooling*
2)
kW
2.2
2.8
3.6
Btu/h
7,500
9,500
12,200
Heating*
3)
kW
2.5
3.2
4.0
Btu/h
8,500
10,900
13,600
Condensate (with High fan speed)
Liters/h
1.12
1.44
1.91
Power
Input
W
25
*5)
25
*5)
30
*5)
Running Current
A
0.16
*5)
0.16
*5)
0.18
*5)
Sound Level
Sound Pressure *
4)
dB(A)
43
44
44
Fan
Type
-
Crossflow fan
Crossflow fan
Crossflow fan
Motor
Model
-
YFK-8-4-SX06
YFK-8-4-SX06
YFK-8-4-SX06
Type
-
Feedback SSR
Feedback SSR
Feedback SSR
Output
W
-
-
-
Airflow Rate
Cooling (High)
m
3
/min
7.80
*5)
7.80
*5)
9.30
*5)
Heating (High)
m
3
/min
8.20
*5)
8.20
*5)
9.50
*5)
Refrigerant
Type
-
R410A
R410A
R410A
Control Method
-
EEV
EEV
EEV
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
Fuse
Fuse
Fuse
Piping
Connections
Liquid (Flare)
ø, mm
6.35
6.35
6.35
Gas (Flare)
ø, mm
12.7
12.7
12.7
Drain
ø, mm
ID 18 hose
ID 18 hose
ID 18 hose
Weight
Net Weight
kg
8.3
8.3
8.3
Shipping Weight
kg
11.3
11.3
11.3
Dimensions
Net Dimensions (W x H x D)
mm
825x285x189
825x285x189
825x285x189
Shipping Dimensions (W x H x D)
mm
900x349x252
900x349x252
900x349x252
Functions
Auto Restart
-
O
O
O
Auto Swing
-
O
O
O
Group/Individual Control
-
O
O
O
External Contact Control
-
O
O
O
Trouble Shooting by LED
-
O
O
O
Standard
Accessories
Installation Manual
-
O
O
O
Operation Manual
-
O
O
O
Pattern Sheet for Installation
-
X
X
X
Flexible Drain Hose
-
O
O
O
Filter / Safety Grille
-
Filter (Washable)
Filter (Washable)
Filter (Washable)
Wireless Remote Controller
ARH-5012
ARH-5012
ARH-5012
Optional
Accessories
Wireless Remote Controller
-
MR-DH00
MR-DH00
MR-DH00
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Содержание AM160FNBFEB/EU
Страница 283: ...PCB Diagram and Parts List Samsung Electronics 5 7 5 1 4 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13 ...
Страница 295: ...PCB Diagram and Parts List Samsung Electronics 5 19 5 1 10 Duct type HSP BLDC PCB 1 2 3 4 ...
Страница 297: ...PCB Diagram and Parts List Samsung Electronics 5 21 5 1 11 Duct type Super 1 2 3 5 4 6 9 10 11 12 13 14 15 16 7 8 ...
Страница 299: ...PCB Diagram and Parts List Samsung Electronics 5 23 5 1 12 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8 ...
Страница 307: ...PCB Diagram and Parts List Samsung Electronics 5 31 5 1 15 Wall Mounted type A3050 MAIN 1 2 4 5 6 7 8 10 11 9 12 13 3 ...
Страница 318: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 BIG Duct This Document can not be used without Samsung s authorization ...
Страница 319: ...Wiring Diagram Samsung Electronics 6 5 6 1 5 Ceiling This Document can not be used without Samsung s authorization ...
Страница 320: ...Wiring Diagram 6 6 Samsung Electronics 6 1 6 Console This Document can not be used without Samsung s authorization ...
Страница 328: ...Wiring Diagram 6 14 Samsung Electronics 6 1 14 ERV Plus This Document can not be used without Samsung s authorization ...