7-8
EB 6495-2 EN
Start-up and configuration
1x
Enter
I.1 Analog input AI1
sub-
menu.
The
I.1.1 Input signal
configuration
item is displayed together with its cur-
rent setting:
I.1.1-6
= Pt 100.
1x
Activate the
I.1.1 Input signal
con-
figuration item.
The input signal setting is highlighted:
Pt 100
1x Change setting to
I.1.1-7
(Pt 1000).
1x Confirm setting.
Adjusting the measuring range
1x
Select
AI1.MIN Lower range value
parameter.
The lower range value is already set to
0 °C and does not need to be
changed.
1x
Select
AI1.MAX Upper range val-
ue
parameter.
1x
Activate
AI1.MAX Upper range
value
parameter.
The upper range value setting is high-
lighted: 100.0 °C
…
Keep pressed and change the upper
range value to 200 °C.
1x Confirm setting.
Return to the operating level
4x Return to the operating level.
7.1.3
Adapting the display
direction
The display can be adapted in the following
ways:
−
Changing the controller display
Î
See section 7.1.3.1.
−
Set up additional display
Î
See section 7.1.3.2.
Содержание TROVIS 6495-2
Страница 6: ...EB 6495 2 EN...
Страница 46: ...6 6 EB 6495 2 EN...
Страница 90: ...8 26 EB 6495 2 EN...
Страница 94: ...9 4 EB 6495 2 EN...
Страница 96: ...10 2 EB 6495 2 EN...
Страница 98: ...11 2 EB 6495 2 EN...
Страница 100: ...12 2 EB 6495 2 EN...
Страница 102: ...13 2 EB 6495 2 EN...
Страница 104: ...14 2 EB 6495 2...
Страница 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Страница 108: ...15 4 EB 6495 2 Certificates...
Страница 109: ...EB 6495 2 15 5 Certificates...
Страница 110: ...15 6 EB 6495 2...
Страница 185: ......