7-2
EB 6495-2 EN
Start-up and configuration
Two DIP switches are assigned to each ana
-
log input AI1 to AI4.
−
Both DIP switches on the right: Current
signal (mA or V)
−
Both DIP switches on the left: Resistance
signal (Pt 100 or Pt 1000) or potentiom
-
eter (only with analog input AI2)
5. Determine the control algorithm, e.g.
C.3.1.1
.
6. Assign the output, e.g.
O.1.1-1
.
7. Set the output signal, e.g.
O.1.2-1
.
8. Set the operating direction, e.g.
O.1.3-
1
.
9. Set the restart condition, e.g.
C.4.1-0
.
DIP switches
AI1
AI2
AI3
AI4
mA / V
Pt 100
Pt 1000
mA / V
Pt 100
Pt 1000
Potentiometer
mA / V
Pt 100
Pt 1000
mA / V
Pt 100
Pt 1000
Before an analog input can be configured,
the DIP switches must be set correspondingly.
These switches are used to initially select
whether an input is to accept a current/volt-
age signal (mA, V) or a resistance signal
(Pt 100, Pt 1000, potentiometer). To make
the initial setting effective, both DIP switches
of an analog input must have the same posi-
tion. If just one DIP switch is switched, an er
-
ror message is generated and the digital out-
put for error messages DO7 is activated. The
fault alarm icon is displayed in the operat-
ing level (see the 'Malfunctions' section).
Содержание TROVIS 6495-2
Страница 6: ...EB 6495 2 EN...
Страница 46: ...6 6 EB 6495 2 EN...
Страница 90: ...8 26 EB 6495 2 EN...
Страница 94: ...9 4 EB 6495 2 EN...
Страница 96: ...10 2 EB 6495 2 EN...
Страница 98: ...11 2 EB 6495 2 EN...
Страница 100: ...12 2 EB 6495 2 EN...
Страница 102: ...13 2 EB 6495 2 EN...
Страница 104: ...14 2 EB 6495 2...
Страница 107: ...EB 6495 2 15 3 Certificates TR CU certificate...
Страница 108: ...15 4 EB 6495 2 Certificates...
Страница 109: ...EB 6495 2 15 5 Certificates...
Страница 110: ...15 6 EB 6495 2...
Страница 185: ......