42
EB 5724-8 EN
Annex
CO/PA
Function/
designation
Setting/
adjustment range
15: Set point from program controller
LIM1.F/
LIM2.F
Function
0: None
1:
Source (signal) ≤ LIM1
Source (signal) ≤ LIM2
2:
Source (signal) ≥ LIM1
Source (signal) ≥ LIM2
LIM1.P/
LIM2.P
Switching point
–50 to +150 °C
LIM1.H/
LIM2.H
Hysteresis
0.5 to 10.0 °C
Program controller
A0.1
Behavior when program
has elapsed
1: Control active, last set point is retained
2: Control active, program is repeated cyclically
3:
Control inactive, actuator positioning value is 0 %
4:
Control inactive, actuator positioning value is 100 %
C1 .../C2 ... Controller [1]/controller [2]
Valve position
C1.1/C2.1 Source
0: Actual
value
(process
variable)
=
(C1.a * AI1 + C1.b * AI2 + C1.c * AI3 + C1.d * AI4)
C1.z
1:
Process variable (actual value) = AI1 after function
generation
2:
Process variable (actual value) = AI2 after function
generation
3:
Process variable (actual value) = AI3 after function
generation
4:
Process variable (actual value) = AI4 after function
generation