40
EB 5724-8 EN
Annex
CO/PA
Function/
designation
Setting/
adjustment range
35:
Heating · Follow-up control · Outdoor temperature con
-
trolled, return flow temperature limitation · External set
point decrease with DI4
M0
System code number
50:
Heating · Override control with minimum selection ·
Return flow temperature limitation · Internal set point
decrease
55:
Heating · Override control with minimum selection ·
Outdoor temperature controlled, return flow tempera
-
ture limitation · External set point decrease with DI4
60:
Cooling · Override control with minimum selection ·
Differential temperature with two sensors, return flow
temperature limitation · Start/stop control sequence
65:
Cooling · Override control with minimum selection ·
Differential temperature with two sensors, return flow
temperature limitation · Start/stop control sequence
66: Cooling · Override control for district cooling · Maxi-
mum selection of the set point control · Start/stop con-
trol sequence
70:
Heating · Cascade control · With two sensors · Internal
set point switchover
80:
Cooling · Cascade control · With two sensors · Start/
stop control sequence
95:
Heating · Position transmitter / Fixed set point/fol
-
low-up control · 2–10 V position transmitter / 0–2 V
Fixed set point/follow-up control · Return flow tempera
-
ture limitation, set point decrease with DI3