16
EB 5724-8 EN
Design and principle of operation
Accessories for sensors
−
Mounting kit for a Pt 1000 cable sensor
as contact sensor, order no. 8524-0020
−
Brass thermowell, G ½, immersion length
80 mm, PN 16, order no. 1099-0807
−
CrNiMo steel thermowell, G ½, immer
-
sion length 80 mm, PN 40, order no.
1099-0805
−
CrNiMo steel thermowell, G ½, immer
-
sion length 250 mm, PN 40, order no.
1099-0806
−
Brass thermowell, G ½, immersion length
160 mm, PN 16, order no. 8525-5005
−
CrNiMo steel thermowell, G ½, immer
-
sion length 160 mm, PN 40, order no.
8525-5011
3.6
Technical data
Electric actuator with process
controller
TROVIS
5724-
810
5725-
810
5724-
820
5725-
820
5724-
830
5725-
830
Fail-safe action
With-
out
With
With-
out
With
With-
out
With
Actuator stem
–
Ex-
tends
–
Ex-
tends
–
Ex-
tends
Connection to valve
Force-locking
Form-fit
Rated travel
6 mm
12 mm
15 mm
Transit time for rated travel
35 s
70 s
90 s
Stroking speed
0.18 mm/s
Thrust
700 N 500 N
700 N
500 N
700 N
280 N
Supply voltage
230 V (±10 %), 50 Hz
Power consumption
6 VA
Manual override
With
With-
out
With
With-
out
With
With-
out
Permissible temperatures
1)
Ambient
0
to
+50 °C
Storage
–20
to
+70 °C
Degree of protection (not installed
suspended)
IP 54
Electromagnetic compatibility
According to EN 61000-6-2, EN 61000-6-3 and
EN 61326
Connecting cable length
Two-wire, 5 m
·
Three-wire, 2.5 m