Mounting and start-up
Table 3:
Communication parameters
C P menu
Designation
Setting
U n
Communication unit
o F
Bluetooth module not active
b L
Bluetooth module active
r 4
RS-485 module active
P r
Communication protocol
S P
SSP
The following values are automatically set with
the 'A P' setting: b d = 96, S t = I n
o d
Modbus RTU slave
A P
Automatic protocol detection
A d
Modbus address
(station address)
01 ... .99
01 to 99
00. ... 99.
100 to 199
0.0. ... 4.7.
200 to 247
b d
Baud rate
I 2
1200
24
2400
48
4800
96
9600
I 9
19200
38
38400
S t
Stop and parity bits
I n
1 stop bit, no parity
I E
1 stop bit, even parity
I o
1 stop bit, odd parity
2 n
2 stop bits, no parity
t I
Timeout
0 ... 99
With t = 0 min, timeout is deactivated.
After the adjusted time has elapsed, the
electric actuator returns to closed-loop oper-
ation. Serves as bus failure monitoring.
White
A (incoming)
Brown
B (incoming)
Green
A' (continuing)
Yellow
B' (continuing)
Black
Screen
Fig. 6:
Bus connecting cable with 3-pin round connector (order no. 1380-2689)