![Samson TROVIS 5724-8 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/samson/trovis-5724-8/trovis-5724-8_mounting-and-operating-instructions_4066910033.webp)
EB 5724-8 EN
33
Operation
6.5
Start and stop program
controller
The program controller allows you to define
the set point over time (max. 1 week =
10080 min). Additionally, it is possible to
define the behavior after the program has
run. See A0.1 configuration item in sec
-
Necessary configuration
(see section 10.2)
−
A1.1 = 4 and A1.5 = 0 or
−
A1.1 = 4 and A1.5 = 1 or
−
A1.1 = 4 and A1.5 = 2 or
−
A1.1 = 4 and A1.5 = 3 or
−
A1.1 = 4 and A1.5 = 4
Start and stop program controller
Start and stop program controller.
Restarting the stopped program con-
troller causes the program to continue
running.
Cancel program controller
Cancel program controller.
Restarting the stopped program con-
troller after it has been canceled caus-
es the program to start from the begin-
ning.
6.6
Manually changing the
stem position
TROVIS 5724-8 only
A manual adjustment of the stem position
only makes sense when the power supply is
switched off as the stem position is deter-
mined by the actuator in closed-loop opera-
tion, meaning any manual adjustment would
be automatically corrected by the actuator.
The stem position is changed at the hand-
wheel:
Î
Switch off the supply voltage.
Î
Turn clockwise to extend the actuator
stem (approx. 4 turns for 1 mm travel).
Î
Turn counterclockwise to retract the actu-
ator stem (approx. 4 turns for 1 mm trav
-
el).