38
EB 5724-8 EN
Annex
10.2
Configuration and parameter list
The default setting depends on the selected system code number. A list of all default settings
CO/PA
Function/
designation
Setting/
adjustment range
I …
Inputs and outputs
Universal input I1/Universal input I2/Universal input I3
I1/I2/I3
Function
0: None
1: DI1 not inverted
2: DI1 inverted
3: AI1 (Pt
1000)
AI1.COR/
AI2.COR/
AI3.COR*
Offset AI1
Offset AI2
Offset AI3
–9.9 to +9.9 °C
Function generation AI1/Function generation AI2/Function generation AI3
AI1.I1/
AI2.I1/
AI3.I1
Input signal, point 1
–50 to +149 °C
AI1.O1/
AI2.O1/
AI3.O1
Output signal, point 1
–50 to +150 °C
AI1.I2/
AI2.I2/
AI3.I3
Input signal, point 2
–49 to +150 °C
AI1.O2/
AI2.O2/
AI3.O2
Output signal, point 2
–50 to +150 °C
Universal input I4
I4
Function
0: None
1: DI4 not inverted
2: DI4 inverted
4:
AI4 (0 to 10 V)
AI4.I1
Input signal, point 1
0.0 to 99.9 %
Note
* Parameters are listed in Service folder > Start-up.