EB 5724-8 EN
51
Annex
HR
Designation
Access
Transmission range
Indicating range
Start
End
Start
End
Operating values and settings of controller [2]
46
Actual value before comparator of controller
[2] (PV[2])
R
–500
1500
–50.0
150.0
47
Set point before comparator of controller [2]
(SP[2])
R
–500
1500
–50.0
150.0
48
Set point deviation of controller [2] (SP[2] –
PV[2])
R
–9999
9999
–999.9
999.9
49
Positioning value of controller [2] before char
-
acteristic Y[2]
R
0
1000
0.0
100.0
50
Positioning value of controller [2] after charac
-
teristic YP[2]
R
0
1000
0.0
100.0
51
Set point deviation of controller [2]
R
0
1
0
1
52
Active controller set point [2]
R
0
9
0
9
53
Set point C2.SP
R/W
–500
1500
–50.0
150.0
54
Reserved
R
0
65535
0
65535
55
Reserved
R
0
65535
0
65535
56
Reserved
R
0
65535
0
65535
57
Reserved
R
0
65535
0
65535
CL
Designation COILS (1-bit)
Access
Status 0
Status 1
Operating states
1
Malfunctions
R
No
Yes
2
Internal manual level on the actuator activated
R
No
Yes
3
Enable external manual level (travel adjust-
ment)
R/W
No
Yes
Digital inputs
4
State of digital input 1
R
Off
On
5
State of digital input 2
R
Off
On
6
State of digital input 3
R
Off
On
7
State of digital input 4
R
Off
On