9. Technical data
Inputs
4 sensor inputs
Pt 1000
for
Flow temperature
Outdoor temperature
Return flow temperature
Drinking water temperature
Outputs
Control signal y
Three-step signal: load: 20 to 250 V AC; 0.3 A AC
On/off signal: load: 20 to 250 V AC; 0.3 A AC
Binary output
1 output for pump control, non-floating:
230 V AC, 2 A AC (cos
ϕ >
0.5)
Power supply
230 V AC (
+
10 %/
−
15 %), 48 to 62 Hz,
Power consumption approx. 1 VA
Ambient temperature
Operation
Transportation and storage
0 to 50 °C
−
10 to 60 °C
Degree of protection
IP 40 according to IEC 529
Class of protection
I according to VDE 0106
Degree of contamination
2 according to VDE 0110
Overvoltage category
II according to VDE 0110
Humidity rating
F according to VDE 40040
Noise immunity
According to EN 50082 Part 1
Noise emission
According to EN 50081 Part 1
Weight
Approx. 0.4 kg
EB 5432-1 EN
35
Technical data
Содержание TROVIS 5432