P 3
Min. flow temperature
30.0
0.0...130.0 °C
(Chap. 7.4)
P 4
Max. flow temperature
80.0
20.0...130.0 °C
P 5
Fixed set point
Return flow temperature
50.0
20.0...90.0 °C
(Chap. 7.5)
Setting with code number
P6
Drinking water set point
55.0
20.0...90.0 °C
(Chap. 7.6)
P8
Kp Return flow temp. limit.
1.0
0.1...50.0
P9
Tn Return flow temp. limit.
0
0...999 s
Measured temperatures
t1
Flow temperature
Press control knob = Flow set point (Chap. 7.13)
t2
Outdoor temperature
Press control knob = Delayed outdoor temperature
t3
Return flow temperature
t4
Drinking water temperature
Factory (default) settings in the user level
Time
10:00
00:00 to 23:59
Year
2001
2001 to 2050
Date
1.01
1.01 to 31.12
Heating time schedule
daily or weekly
7:00
to
22:00
00:00 to 24:00
Reference value for room temperature
20.0
10.0 to 30.0
Set point for flow temperature
65.0
0.0 to 130.0
Reduced reference value for room temp.
17.0
10.0 to 30.0
Reduced set point for flow temperature
50.0
0.0 to 130.0
Outdoor temperature
Measured
value
Press control knob =
Delayed outdoor temperature
EB 5432-1 EN
21
Configuration and parameterization