Alternatively, you can wait three seconds until the display stops blinking. The party mode is
activated.
The party mode remains effective until a different reference value or set point is entered.
Even after a power failure, the party mode remains effective.
If you want to end the party mode, turn the control knob counterclockwise one position. Wait
briefly and then turn the knob one position further, then the set reference value or set point
reappears in the display.
4.3 Holiday mode
If you switch off the heating, but would like the frost protection to remain active, proceed as
follows:
Turn the control knob counterclockwise until
HolidAY
appears in the display.
Press the knob to acknowledge the setting.
Alternatively, you can wait three seconds until the display
stops blinking. The holiday mode is activated.
The frost protection function comes into effect when the outdoor temperature falls below 3 °C
when the weather-compensated control is activated or the flow temperature falls below 5 °C
when the fixed set point control is activated. The circulation pump is activated and the flow
temperature is controlled to 20 °C. During fixed set point control, the circulation pump runs
continuously.
Note:
The frost protection function is not active when the controller is set to manual
operation.
The holiday mode setting remains effective until a different reference value or set point is en-
tered. Even after a power failure, the holiday mode remains effective.
If you want to end the holiday mode, turn the control knob clockwise one position. Wait
briefly and then turn the knob one position further, then the set reference value or set point
reappears in the display.
10
EB 5432-1 EN
Setting options on the display level
Содержание TROVIS 5432
Страница 37: ...EB 5432 1 EN 37...