7.10 Manual operation
Set F2 to 1 = ON
Manual operation is carried out as stipulated in DIN EN 12098-1. The circulation pump is
activated.
The controller does not issue a control signal in either on/off control or three-step control for
the heating circuits control valve.
Display:
Depending on the operating mode, the reference value for
room temperature or flow temperature set point appears in
the display.
Note:
The frost protection function is not activated when the
controller is in manaul operation.
7.11 Pump seizure protection
If the circulation pump has not been activated within 24 hours, it is force-operated by the
controller at 12:00 hrs for one minute.
EB 5432-1 EN
29
Description of the controller functions