8.4 Connecting the sensors
Connect cables with a cross-section of min. 2x 0.5 mm
2
to the terminals of the controller.
8.4.1 Pt 1000 sensor values
°C
35
30
25
20
15
10
5
0
5
10
Ohm
862.5
882.2
901.9
921.6
941.2
960.9
980.4
1000.0
1019.5
1039.0
°C
15
20
25
30
35
40
45
50
55
60
Ohm
1058.5
1077.9
1097.3
1116.7
1136.1
1155.4
1174.7
1194.0
1213.2
1232.4
°C
65
70
75
80
85
90
95
100
105
110
Ohm
1251.6
1270.7
1289.8
1308.9
1328.0
1347.0
1366.0
1385.0
1403.9
1422.9
°C
115
120
125
130
135
140
145
150
Ohm
1441.7
1460.6
1479.4
1498.2
1517.0
1535.8
1554.5
1573.1
8.5 Connecting the actuator
Connect the cable (suitable for damp locations) with a cross-section of min. 1.5 mm
2
to the
terminals of the controller output.
Following this, we recommend that you check the operating direction and the correct connec-
tion (polarity) of the actuator.
For this purpose, after you have connected the power supply, increase the reference value
for room temperature considerably for a short period. This should lead the controller to open
the heating valve with its OPEN control signal (+). When the reference value is reduced, the
heating valve should close with the CLOSE control signal (-).
8.6 Connecting the pump
Connect the cable with a cross-section of min. 1.5 mm
2
to the terminals of the controller.
34
EB 5432-1 EN
Installation and electrical connections