5.3 Setting the reference value for room temperature or the flow
temperature set point for rated and reduced operation
If you are not on the user level, press the control knob for
three seconds.
At first, the time appears in the display.
Turn the control knob clockwise two positions.
In the operating mode "
Weather-compensated control
",
the
reference value for room temperature
for rated oper-
ation (time-of-use) appears in the display.
The default value is 20.0.
In the operating mode "
Fixed set point control
", the
flow
temperature set point
for rated operation (time-of-use) ap-
pears in the display.
The default value is 65.0 °C.
If you want to change the currently displayed value:
Press the control knob. The symbols at the bottom of the dis-
play start to blink.
Turn the control knob to set the required value and press the
knob to acknowledge the set value.
Turn the control knob one position further to access the ref-
erence value for room temperature or flow temperature set
point for reduced operation (time of non-use).
In the operating mode "
Weather-compensated control
",
the
reference value for room temperature
for reduced
operation (time of non-use) appears in the display.
The default value is 17.0.
EB 5432-1 EN
17
Setting options on the user level