SAMLEX AMERICA INC. | 95
SECTION 15 |
Specifications
MODEL NO.
PSR-1200-24
PSR-1200-48
AC OUTPUT IN INVERTER MODE
OUTPUT VOLTAGE
100 - 120 VAC (User selectable) ; Default: 120 VAC
OUTPUT FREQUENCY
45 - 65 Hz (User Selectable) ; Default: 60Hz
TYPE & OUTPUT WAVE FORM
High Frequency Type ; Pure Sine Wave
TOTAL HARMONIC DISTORTION (THD) OF
OUTPUT WAVEFORM
< 2%
CONTINUOUS OUTPUT POWER
1200W
SURGE OUTPUT POWER
2000W
PEAK EFFICIENCY
> 88%
> 90%
NEUTRAL ISOLATION
•
Neutral bonded to Chassis Ground when Inverter is supplying the load
•
Neutral isolated from Chassis Ground when Grid is supplying the load
AC OUTPUT IN BYPASS MODE
OUTPUT VOLTAGE
Same as external AC input source
TYPE OF OUTPUT WAVE FORM
Same as external AC input source
THD OF OUTPUT WAVEFORM
Same as external AC input source
CONTINUOUS OUTPUT POWER
1200W continuous (Protected by 15A AC input breaker)
RATING OF TRANSFER RELAY
16A
TRANSFER RELAY SWITCHING TIME
< 8ms
TRANSFER TYPE
Synchronized or Unsynchronized (User selectable)
NEUTRAL ISOLATION
Neutral and Chassis Ground are isolated through internal relay
DC/AC INPUT
NOMINAL DC INPUT VOLTAGE
24 VDC
48 VDC
DC INPUT VOLTAGE RANGE
20 - 34 VDC
40 - 60 VDC
DC INPUT NO LOAD CURRENT
< 0.6A
< 0.5A
AC INPUT FROM GRID/GENERATOR
100 - 120 VAC, 50/60 Hz
DISPLAY
LCD
Alphanumeric: 2 lines x 16 characters each
LEDS
4 LEDS: AC GRID ; INVERTER ; BYPASS ; ALARM
LOCAL CONTROL & MONITORING
MODE AND PARAMETER SETUP
Through Menus displayed on the LCD screen
MONITORING OPERATING STATUS
Through LCD screen and 4 LEDs
REMOTE CONTROL
AND MONITORING
PARAMETER SETUP AND
MONITORING USING USB / RS-232
Through computer screen using ACII coded commands
MONITORING USING
ETHERNET/SNMP
Through computer’s Web Browser and Ethernet connection
• E-mail notification of faults and alarms
Notification of faults and alarms through Ethernet / SNMP Trap Messaging
WIRED ON/OFF CONTROL
THROUGH TERMINALS MARKED
ENB, ENB AND GND
To switch ON:
• Ex 10 to 40VDC fed to ENB
and GND (< 6mA)
• Short ENB and GND
• Battery Positive fed to ENB
To switch ON:
• Ex 20 to 60VDC fed to ENB
and GND (< 6mA)
• Short ENB and GND
• Battery Positive fed to ENB
WIRED SIGNALLING Signaling of faults and alarms through SPDT relay contact switching (no voltage)
• Relay contact rating: 240 VAC, 16A
PROTECTIONS
COOLING
Three load / temperature controlled fans:
• Switch ON when output load is >300W and switch OFF when the load reduces
to < 280W
• Switch ON when internal heat sink temperature is ≥ 50°C and switch OFF when
temperature reduces to ≤ 45°C
DC INPUT UNDER VOLTAGE (UV) ALARM
17.0 to 23.0 VDC ; Default: 21.5 VDC
(Auto reset at 0.5V > the set voltage)
34.0 to 46.0 VDC ; Default: 43.0 VDC
(Auto reset at 1.0V > the set voltage)
DC INPUT OVER VOLTAGE (OV) ALARM
25.0 to 35.0VDC ; Default: 33.0VDC
(Auto reset at 0.5V < the set voltage)
50.0 to 62.0 VDC ; Default: 56.0 VDC
(Auto reset at 1.0V < the set voltage)