SAMLEX AMERICA INC. | 69
TABLE 11.1 PROTECTIONS RESULTING IN SHUT DOWN OF INVERTER (Continued)
Protection and reset
AC GRID
input
conditions
Front panel
LED marked
“AC GRID”
(2, Fig 6.1)
Front panel
LED marked
“INVERTER”
(3, Fig 6.1)
Front
panel LED
marked
“BYPASS”
(4, Fig 6.1)
Front Panel
LED marked
“ALARM”
(5, Fig 6.1)
will be Red
Buzzer
(Parameter
“Buzzer
Setup” set
to Enabled)
Relay for
remote sign-
aling of alarm
(Parameter
Relay Setup
set to
Enabled)
LCD Display
Short circuit Protection
• Load draws higher than 24A
for 1.2 sec, or
• Output voltage drops to
80VAC for 1.2 sec
Manual Reset
Inverter will be latched in
shut down condition. To reset,
switch OFF by witching the
3-Position Rocker Switch
(1, Fig 6.1) to OFF position.
Wait for 10 sec and switch
on again
AC Grid
input
available
Green/
Orange
Red
Green
Orange
On
Energized
** Warning **
Short circuit
protection!!
AC Grid
input not
available
Off
Red
Off
Orange
On
Energized
Over Temperature Protection
• Temperature of either of
two hot-spots near two heat
sinks (sensed by NTC1 and
NTC2) is higher than 105°C
Automatic reset:
When the temperature drops
to 85°C
AC Grid
input
available
Green/
Orange
Red
Green
Orange
On
Energized
** Warning **
Over
temperature
protection!!
AC Grid
input not
available
Off
Red
Off
Orange
On
Energized
Over Voltage Protection
• DC input voltage is higher
than the set value of param-
eter “OVP Setting”
Automatic reset:
§
PSR-1200-24: 0.5V lower
than “ OVP Setting”
§
PSR-1200-48: 1.0V lower
than “ OVP Setting” value
AC Grid
input
available
Green/
Orange
Red
Green
Orange
On
Energized
** Warning **
Over voltage
protection!!
AC Grid
input not
available
Off
Red
Off
Orange
On
Energized
Under Voltage Protection
• DC input voltage is lower than
the set value of parameter
“UVP Setting”
Automatic reset:
§
PSR-1200-24: 0.5V higher
than “UVP Setting”
§
PSR-1200-48: 1.0V higher
than “UVP Setting” value
AC Grid
input
available
Green/
Orange
Red
Green
Orange
On
Energized
** Warning **
Under voltage
protection!!
AC Grid
input not
available
Off
Red
Off
Orange
On
Energized
SECTION 11 |
Protections and Alarms