70 | SAMLEX AMERICA INC.
TABLE 11.2 ALARMS (UNIT DOES NOT SHUTDOWN)
Protection and reset
AC GRID
input
conditions
Front panel
LED marked
“AC GRID”
(2, Fig 6.1)
Front panel
LED marked
“INVERTER”
(3, Fig 6.1)
Front
panel LED
marked
“BYPASS”
(4, Fig 6.1)
Front Panel
LED marked
“ALARM”
(5, Fig 6.1)
will be Red
Buzzer
(Parameter
“Buzzer
Setup” set
to Enabled)
Relay for
remote sign-
aling of alarm
(Parameter
Relay Setup
set to
Enabled)
LCD Display
Fan Failure
• Fan speed drops of or fan
stops completely
AC Grid
input
available
Green/
Orange
Green
Green
Orange
On
Energized
** Warning **
Fan failure!!
AC Grid
input not
available
Off
Green
Off
Orange
On
Energized
Over Voltage Alarm
• DC input voltage is higher
than the value of parameter
“OV Alarm”
Automatic reset:
§
PSR-1200-24: 0.5V lower
than “ OV Alarm”
§
PSR-1200-48: 1.0V lower
than “ OV Alarm” value
AC Grid
input
available
Green/
Orange
Green
Green
Orange
On
Energized
** Warning **
Over voltage
detected!!
AC Grid
input not
available
Off
Green
Off
Orange
On
Energized
Under Voltage Alarm
• DC input voltage is lower
than the value of parameter
“UV Alarm”
Automatic reset:
§
PSR-1200-24: 0.5V higher
than “ UV Alarm”
§
PSR-1200-48: 1.0V higher
than “ UV Alarm” value
AC Grid
input
available
Green/
Orange
Green
Green
Orange
On
Energized
** Warning **
Under
voltage
detected!!
AC Grid
input not
available
Off
Green
Off
Orange
On
Energized
11.3 WEB BROWSER BASED REMOTE MONITORING OF ALARM AND FAULT CONDITIONS
USING WIRED USB / RS-232 SERIAL COMMUNICATION AND INTERNET
8 types of protection / alarm warnings shown in Tables 11.1 and 11.2 can be monitored remotely through a
computer as follows:
• Using Wired USB / RS-232 Serial Communication Protocol : Refer to Section 12
§
Connect the unit to the remote computer through USB / RS-232 cable
§
Load Web Browser based Terminal Emulator software on the computer.
§
Use specified text based status queries from the Command Line (See Command Table at Section 12.6)
• Using Ethernet connection (Internet): Refer to Section 13
§
Connect the Ethernet Port on the unit to Internet Router
§
On the remote computer, enter the IP Address of the unit
SECTION 11 |
Protections and Alarms