SAMLEX AMERICA INC. | 45
SECTION 8 |
Installation
8.5.1 AC Input and Output Connections
8.5.1.1 AC Inlet
AC input is fed through 120 VAC Male Power Inlet (IEC 60320 C14 Connector) (18, Fig 6.2).
AC Power cord with mating Female IEC 60320 C13 Connector on one end and NEMA5-15P Plug on the
other end has been provided with the unit.
8.5.1.2 AC Outlets
AC output is provided through NEMA5-20R, Duplex AC outlets (17, Fig 6.2).
8.5.2 Bonding of AC Output Neutral to Equipment Ground (Metal Chassis Ground)
The Neutral slots of the NEMA5-20R Duplex Outlets (17, Fig 6.2) are bonded to the Equipment Ground (metal
chassis Ground) of the inverter through Neutral to Ground Bond Switching Relay resulting in the following
N-G bond conditions:
• Output Neutral and the metal chassis Ground are bonded when Inverter is supplying power to the load.
• Output Neutral and the metal chassis Ground are isolated when AC GRID is being bypassed.
See further details at Section 5.4.3.
8.6 GROUNDING TO EARTH OR TO OTHER DESIGNATED GROUND
For safety, ground the metal chassis of the inverter to the Earth Ground or to the other designated
Ground. An equipment grounding Lug (16, Fig 6.2) has been provided for grounding the metal chassis of
the inverter to the Earth Ground or to the other appropriate Ground.
When using the inverter in a building, connect a 10 mm
2
or AWG #8 insulated stranded copper wire from
the above equipment grounding lug to the Earth Ground connection (a connection that connects to the
Ground Rod or to the water pipe or to another connection that is solidly bonded to the Earth Ground).
The connections must be tight against bare metal. Use star washers to penetrate paint and corrosion.
8.7 WIRED REMOTE ON / OFF CONTROL FOR INVERTER SECTION
4 methods are available to switch ON and switch OFF the Inverter Section using external, wired switching
control. Please refer to Section 5.7 for details.
IMPORTANT NOTE: For activation of this wired remote ON / OFF control function, the 3-Position Rocher
Switch (1, Fig 6.1) on the Front Panel has to be pressed down towards position marked "EXT. Switch".
8.8 2-WIRE REMOTE MONITORING OF ALARMS / FAULTS
Single Pole Double Throw (SPDT) relay contacts have been provided for remote signalling of 6 types of
alarms / fault conditions. Refer to Section 5.8 for details.