58 | SAMLEX AMERICA INC.
10.2.2 Main Menu for Parameter Setup Groups 1-6 > Group 2 “Input Setup” > Sub-Menu for
“Input Setup”
10.2.2.1 “a. OVP Setting”: Sets the Over Voltage Protection (OVP) threshold on the DC input side. If the DC
input voltage rises to the programmed threshold in Inverting Mode, the AC output of the Inverter will be
shut down.
Parameter
Programmable Range
Default
a. OVP Setting
(
Over Voltage Protection Setting)
PSR-1200-24: 25.0 to 35.0 VDC
34.0 VDC
PSR-1200-48: 50.0 to 62.0 VDC
60.0 VDC
10.2.2.2 “b. OVP Recovery”: Sets the voltage threshold for automatic recovery / reset from OVP condition
explained at Section 10.2.2.1 above.
Parameter
Programmable Range
Default
b. OVP Recovery
(Over Voltage Protection Recovery)
PSR-1200-24: 24.5 to 34.5 VDC
33.0 VDC
PSR-1200-48: 49.0 to 61.0 VDC
58.0 VDC
10.2.2.3 “c. UVP Setting”: Sets the Under Voltage Protection (UVP) threshold on the DC input side. If the DC
input voltage falls to the programmed threshold or below continuously for 0.1 sec in Inverting Mode, the AC
output of the Inverter will be shut down.
Parameter
Programmable Range
Default
c. UVP Setting
(Under Voltage Protection Setting)
PSR-1200-24: 17.0 to 23.0 VDC
20.0 VDC
PSR-1200-48: 34.0 to 46.0 VDC
40.0 VDC
10.2.2.4 “d. UVP Recovery”: Sets the voltage threshold for automatic recovery / reset from UVP condition
explained at Section 11.2.2.3 above.
Parameter
Programmable Range
Default
d. UVP Recovery
(Under Voltage Protection Recovery)
PSR-1200-24: 17.5 to 23.5 VDC
23.0 VDC
PSR-1200-48: 35.0 to 47.0 VDC
46.0 VDC
10.2.2.5 “e. OV Alarm”: Sets the voltage threshold for alarm for Over Voltage (OV) on the DC input side.
If the DC input voltage rises to the programmed threshold, the following indications will be activated
(The Inverter Section will not shut down at this stage but will shut down if the voltage further rises to the
programmed threshold of “OVP Setting” (See Section 10.2.2.1):
•
LCD Screen (6, Fig 6.1) will display “** Warning** Over voltage detected!!”
•
LED marked “ALARM” (5, Fig 6.1) will be lighted (Orange)
•
Buzzer Alarm will be activated (if “Enabled” – See Buzzer Setup at 10.2.1.5). At the same time, the
SPDT Signaling Relay will be activated (when “Enabled” – Relay Setting at Section 10.1.2.6)
Parameter
Programmable Range
Default
e. OV Alarm
(Over Voltage Alarm)
PSR-1200-24: 25.0 to 35.0 VDC
33.0 VDC
PSR-1200-48: 50.0 to 62.0 VDC
56.0 VDC
SECTION 10 |
Programming of Operating Parameters