82 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 83
5.4.2 Uploading Saved Parameters
If there is a “xxxx_yyy.cfg” file in the SD card with stored programmed parameters, then on
inserting the card, the Remote Control will ask to upload the Config File. Press Enter Button
to confirm or Back Key to cancel.
U p l o a d
c o n f ?
Y e s = E n t e r
k e y
N o = B a c k
k e y
• Asks to confirm or cancel uploading of saved parameters.
• Choose Yes by pressing Enter Key.
U p l o a d
c o n f
1 %
Configuration uploading.
SECTION 6 | Monitoring of Operation
Using LED and Buzzer
TABLE 6.1 LED & BUZZER INDICATIONS FOR OPERATION MONITORING
Status
Blue LED "Status"
Red LED "Fault"
Buzzer (See Note 1)
Seen during Power-On Sequence
Indicates completion of Power-On
Sequence after Power ON/OFF Button
is pressed for 2 sec
Blink 3 times
OFF
OFF
Seen during Power-Off Sequence
Indicates completion of Power-Off
Sequence after Power ON/OFF Button
is pressed for 5 sec
ON
ON
OFF
Normal charging
Blink once per sec
OFF
OFF
Equalization charging
Blink twice per sec
OFF
OFF
Inverting
ON
OFF
Beep per 3 second
(Default OFF)
Low battery alarm
ON
Blink once per sec
Beep per second
Power saving
Blink once per 3 sec
OFF
OFF
Standby
Blink once per 5 sec
OFF
OFF
Fault
OFF
ON
ON
NOTE:
Buzzer is available only in EVO
TM
Inverter/Charger. There is no buzzer in Remote Control
EVO-RC-PLUS.
SECTION 5 |
SD Card
Содержание Evolution Series