Parameter Setup
4.4 GROUP 1 PARAMETER SETUP: CHARGE CURVE
4.4.1 Programming Ranges and Default / Factory Preset Values or Parameters
Under - Group 1 - CHARGE CURVE
Table 4.3 below gives details of programming ranges and default values of parameters under
Group 1 - "CHARGE CURVE". Refer to Fig 4.2 under Section 4.1.3.1 for the Menu Map for
navigating through various parameters under this Group.
NOTE:
Value shown within brackets "( )" indicate the "Default Setting".
Table 4.3 Group 1 Parameter Set Up: CHARGE CURVE (Refer to Menu Map at Fig 4.2, Section 4.1.3.1)
Screen
No.
Parameter
EVO-1212F
EVO-1212F-HW EVO-2212
EVO-3012
EVO-1224F
EVO-1224F-HW EVO-2224
EVO-4024
1
“BULK CURRENT”
(Bulk Charge
Current “Io”)
0 – 60A
(20A)
0 –
100A
(40A)
0 – 130A
(40A)
0 – 40A
(15A)
0 – 70A
(40A)
0 – 110A
(40A)
2
“ABSORP VOLTAGE”
(Absorption Voltage)
13.50 – 16.00V
(14.40V)
27.00 – 32.00V
(28.80V)
3
“EQUALIZE VOLTAGE”
(Equalization Voltage)
14.00 – 16.00V
(14.40V)
28.00 – 32.00V
(28.80V)
4
“FLOAT VOLTAGE”
(Float Voltage)
13.00 – 15.00V
(13.50V)
26.00 – 30.00V
(27.00V)
5
“COMPENSATE”
(Temperature
Compensation)
-3mV to -5mV/°C/Cell
(-4mV/°C/Cell)
6
“BATT OVER VOLT”
(Battery Over Voltage
Shut Down)
14.00 – 17.00V
(16.00V)
28.00 – 35.00V
(32.00V)
7
“RESET VOLTAGE”
(Battery Low Voltage
Reset)
12.00 – 17.00V
(14.00V)
24.00 – 35.00V
(28.00V)
8
“LOW VOLT ALARM”
(Battery Low Voltage
Alarm)
9.50 – 12.50V
(11.00V)
19.00 – 25.00V
(22.00V)
9
“BATT LOW VOLTAGE”
(Battery Low Voltage
Shut Down)
>9.00 – 12.00V
(10.50V)
>18.00 – 24.00V
(21.00V)
10
“LV DETECT TIME”
(Detected Time to
Qualify as Battery Low
Voltage Shut Down
Condition)
0 – 600 sec
(10 sec)
11
“LV CUT OFF TIME”
(Time in Low Voltage
Shut Down Condition
before Shut Down is
Activated)
0 – 7200 sec
(1200 sec)