4.8 GROUP 5 PARAMETER SET UP: OTHER FUNCTIONS
Please refer to Parameters under Group 5 at Fig 4.2. Details of Parameter set up are given below:
4.8.1 Programming Ranges and Default / Factory Preset Values of Parameters
under Group 5 - OTHER FUNCTION
Table 4.8 below gives details of programming ranges and default values of parameters under
Group 5 - OTHER FUNCTION. Refer to Fig 4.4 under Section 4.1.3.3 for Menu Map for navi-
gating through the various parameters under this Group.
Table 4.8 Group 5 Parameter Set Up: INPUT LOW LIMIT
(Refer to Menu Map at Fig 4.4, Section 4.1.3.3)
Screen
No.
Parameter
Setting range
EVO-1212F
EVO-1212F-HW EVO-2212
EVO-3012
EVO-1224F
EVO-1224F-HW EVO-2224
EVO-4024
1
POWER SAVING
0 = Disable , 1 = Enable
(0 = Disable)
2
ENTER POINT
4 - 50W
(6W)
4 - 50W
(6W)
4 - 50W
(8W)
4 - 50W
(6W)
4 - 50W
(6W)
4 - 50W
(8W)
3
WAKE UP POINT
4 - 50W
(7W)
4 - 50W
(7W)
4 - 50W
(10W)
4 - 50W
(7W)
4 - 50W
(7W)
4 - 50W
(10W)
4
REMOTE SWITCH
0 = Button Type , 1 = Switch Type
(0 = Button Type)
5
RELAY FUNCTION
0 = Charger / Other
1 = Normal / Fault
2 = Generator 0
3 = Generator 1
0 = Charger / Other
1 = Normal / Fault
2 = Generator 0
3 = Generator 1
6
COMM ID
1 - 255
(1)
7
BUZZER
0 = OFF , 1 = ON
(1 = ON)
8
DISCHARGE BEEP
0 = OFF , 1 = ON
(0 = ON)
9
DEFAULT RESET
0 = No , 1 = Yes
(0 = No)
10
DATALOG TIME
0 = Disable, 1 = 1 sec, 2 = 10 sec, 3 = 30 sec,
4 = 1 min, 5 = 5 min, 6 = 10 min
(1 = 1 sec)
11
PARAMETER SAVE
0 = No , 1 = Yes
(0 = No)
12
TEMP UNIT
0 = °C ; 1 = °F
(0 = °C)
13
PASSWORD
DISABLE
0 = No , 1 = Yes
(0 = No)
NOTES for Table 4.8:
1. Values with brackets "( )" show the Default Setting.
2. RELAY FUNCTION is not available for EVO-1212F / 1212F-HW / 1224F / 1224F-HW
SECTION 4 |
Parameter Setup