4.1.3.2 "Select Parameter" Menu Maps for (i) Parameter Group 2: INPUT
SETTING, (ii) Parameter Group 3: INPUT LOW LIMIT and (iii) Parameter
Group 4: INPUT HIGH LIMIT.
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
D E F A U L T F R E Q
0 = 6 0 H z
Screen
No. 1
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
* G R I D M A X C U R R E N T
2 0 . 0 0 A
Screen
No. 2
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
G E N M A X C U R R E N T
3 0 . 0 0 A
Screen
No. 3
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
H I G H R E S E T
6 4 . 0 0 H z
Screen
No. 5
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
L O W C U T O F F
5 5 . 0 0 H z
Screen
No. 6
ð
ð
ð
ð
ð
ð
ð
ð
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
H I G H C U T O F F
6 5 . 0 0 H z
Screen
No. 4
ð
ð
S e l e c t
P a r a m e t e r
I N P U T S E T T I N G
*
L O W R E S E T
5 6 . 0 0 H z
Screen
No. 7
ð
ð
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
R E S E T V O L T A G E
1 0 5 . 0 V
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
C U T O F F
V O L T 1
1 0 0 . 0 V
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
D E T E C T T I M E 1
3 0 0
c y c l e
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
D E T E C T T I M E 2
6 0
c y c l e
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
C U T O F F
V O L T 3
9 0 . 0 V
ð
ð
ð
ð
ð
ð
ð
ð
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
C U T O F F
V O L T 2
9 5 . 0 V
ð
ð
S e l e c t
P a r a m e t e r
I N P U T L O W L I M I T
*
D E T E C T T I M E 3
1
c y c l e
ð
ð
NOTES:
1. Value shown in the 4
th
line of the display screen is the default / factory pre-set values (EVO-1212F / 1212F-HW
in this case). For the default / factory pre-set values and additional programming details for the other Models,
refer to
(i) Table 4.5 (Section 4.5) for “INPUT SETTING”, (ii) Table 4.6 (Section 4.6) for “INPUT LOW LIMIT” and
(iii) Table 4.7 (Section 4.7) for “INPUT HIGH LIMIT”.
2. Asterisk sign * in the beginning of the 3rd line of the display screen points that the parameter shown in this
line will be selected for further programming when the Enter Key is pressed
3. Screen No. 3 is displayed only in Model Nos. that have Generator input terminals (EVO-2212 / 3012 / 2224 /
4024). These screens are NOT displayed in EVO-1212F / 1212F-HW and EVO-1224F / 1224F-HW
4. Use Up
ñ
and Down
ò
Keys to navigate to the desired screen.
Up Key
Down Key
ð ð
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
R E S E T V O L T A G E
1 2 5 . 0 V
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
C U T O F F
V O L T 1
1 3 5 . 0 V
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
D E T E C T T I M E 1
6 0
c y c l e
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
D E T E C T T I M E 2
1 5
c y c l e
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
C U T O F F
V O L T 3
1 4 5 . 0 V
ð
ð
ð
ð
ð
ð
ð
ð
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
C U T O F F
V O L T 2
1 4 0 . 0 V
ð
ð
S e l e c t
P a r a m e t e r
I N P U T H I G H L I M I T
*
D E T E C T T I M E 3
1
c y c l e
ð
ð
Screen
No. 1
Screen
No. 2
Screen
No. 3
Screen
No. 5
Screen
No. 6
Screen
No. 4
Screen
No. 7
Screen
No. 1
Screen
No. 2
Screen
No. 3
Screen
No. 5
Screen
No. 6
Screen
No. 4
Screen
No. 7
Parameter Group 2
"INPUT SETTING"
Parameter Group 3
"INPUT LOW LIMIT"
Parameter Group 4
"INPUT HIGH LIMIT"
Fig 4.3 "Select Parameter" Menu Maps for (i) Parameter Group 2:
INPUT SETTING, (ii) Parameter Group 3: INPUT LOW LIMIT and
(iii) Parameter Group 4: INPUT HIGH LIMIT.
SECTION 4 |
Parameter Setup
See NOTE 3
Содержание Evolution Series
Страница 89: ...SAMLEX AMERICA INC 89 Notes...
Страница 90: ...90 SAMLEX AMERICA INC Notes...
Страница 91: ...SAMLEX AMERICA INC 91 Notes...