44 | SAMLEX AMERICA INC.
SECTION 4 |
Parameter Setup
4.4.2.5 COMPENSATE
(Table 4.3, Screen No. 5)
This parameter sets the temperature compensation for the battery. The operational range of
the EVO
TM
Inverter/Charger is -20°C to 60°C.
This compensation voltage will affect the Absorption Voltage/Equalize Voltage/Floating Voltage/
Batt Over Volt/Restart Voltage/Low Volt Alarm/Batt Low Voltage when the Temperature Sensor is
installed on the battery (see Fig 2.5 in the Owner's Manual for Evolution
TM
Series Inverter/Charger).
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B U L K C U R R E N T
2 0 A
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
C O M P E N S A T E
4 m V /
°
C / C e l l
P a s s w o r d
k e y
i n
0 0 0 0
Enter Key
Down Key x 4 times
Enter Key
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
C O M P E N S A T E
4 m V /
°
C / C e l l
Password 8052
See Section 4.3.1
4.4.2.6 BATT OVER VOLT
(Table 4.3, Screen No. 6)
This parameter sets the upper battery voltage threshold at which inverting / charging
operations are switched OFF to protect the unit against damage due to battery overvoltage:
•
AC input is not available and EVO
TM
Inverter/Charger is operating in Inverting
Mode:
When the battery voltage rises to the set upper threshold of “BATT OVER VOLT”,
the Inverter Section will be shut down and fault message “Battery over voltage!” will be
displayed on the LCD screen. The Blue LED marked “Status” will switch OFF and the Red
LED marked “Fault” will remain ON steady. The buzzer on EVO
TM
Inverter/Charger will beep
steady. The fault will be cleared automatically when the battery voltage drops to 0.5V
below the set upper threshold of “BATT OVER VOLT”
•
AC input is available and EVO
TM
Inverter/Charger is operating in Charging Mode:
When the battery voltage rises to the set upper threshold of “BATT OVER VOLT”, the Transfer
Relay will be de-energized, charging and pass through will be stopped and PWM drive to the
Inverter Section will be switched OFF. Fault message “Battery over voltage!” will be displayed
on the LCD screen. The Blue LED marked “Status” will switch OFF and the Red LED marked
“Fault” will remain ON steady. The Buzzer on EVO
TM
Inverter/Charger will beep steady. The fault
will be cleared automatically when the battery voltage drops to 0.5V below to the set upper
threshold of “BATT OVER VOLT”. The unit will start in Inverting Mode, synchronize with the AC
input and then, the Transfer Relay will be energized to transfer to AC input at zero crossing.
The unit will, thus, resume operation in “Charging Mode”.
S e l e c t
G r o u p
*
C H A R G E
C U R V E
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B U L K C U R R E N T
2 0 A
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B A T T
O V E R
V O L T
1 6 . 0 0 V
P a s s w o r d
k e y
i n
0 0 0 0
Enter Key
Down Key x 5 times
Enter Key
ð
S e l e c t
P a r a m e t e r
C H A R G E
C U R V E
*
B A T T
O V E R
V O L T
1 6 . 0 0 V
Password 8052
See Section 4.3.1
ð
Enter Key
See Table 4.3, Screen 5
for programmable range
ð
Enter Key
See Table 4.3, Screen 6
for programmable range