ESS Inverter User Manual
Smart Load Output Mode
1.
Go to
Hybrid Setting > GEN Port
page and choose
Smart Load Output
as below.
Smart Load Output Mode:
Under this mode, the GEN Port works as an output port for the Smart Load
connected to the GEN terminal.
2.
All parameters have been set by default.
Minimum PV power of Smart Load On (W):
Minimum PV input power above which the Smart Load
will switch on. Also, the Battery SOC should exceed the setting value (%) simultaneously and then the
Smart Load will switch on.
Battery SOC of Smart Load On (%):
Battery SOC above which the Smart Load will switch on. Also,
the PV input power should exceed the setting value(Power) simultaneously and then the Smart Load will
switch on.
Battery SOC of Smart Load Off (%):
Battery SOC below which the Smart Load will switch off.
Always On with Grid:
When click “Always On with Grid” the Smart Load will switch on when the grid
is present.
The default values of
Smart Load Output
are as below:
3.
If the values are set as described above, the situations are as follows:
When
Always On with Grid
is ON, if the grid is present, the Smart Load will be ON all the time. It is not
affected by the change of above parameters. If the grid is not present, the Smart Load will be OFF.
When
Always On with Grid
is OFF, if the PV power ≥ 500W and the Battery SOC ≥ 100%, the GEN Port
function will be enabled and the Smart Load will be ON. If the PV power
<
500W or the Battery SOC
<
80%, the GEN Port function will be disabled and the Smart Load will be OFF.