Installation
14
ESS Inverter User Manual
≤15°
Upright
Lean back ≤15°
Upside-down
Horizontally
350mm
350mm
Installation along the same line for multiple inverter
3.2.2
Mounting Requirements
Mount the inverter vertically or tilted backward by max 15°. The device can not be installed
with a wrong mode and the connection area must point downward.
3.2.3
Installation Space Requirements
To ensure the inverter normally and easy to operate, there are requirements on available spaces of the
inverter, e.g. to keep enough clearance. Refer to the following figures.
≥500
Above: 500mm
Below: 600mm
Front: 1000mm
Left side: 200mm
Right side: 350mm
≥600